6.4 Reflectometry
  
(Measurement of reflection coefficient, return loss, and SWR)
  >>> 
work in progress.
  
  Reflectometry:
  
  One of the principal applications of the impedance bridge is
  the measurement of forward and reflected power in transmission
  lines; this usually being expressed in terms of SWR or return
  loss (to be defined shortly). The bridge however, cannot measure
  reflections, it can only measure quantities which can be derived
  from voltage and current. The ratio of forward to reflected power
  in a line is a function of the load impedance and the characteristic
  impedance; and, in the case of a lossless line at least, remains
  constant throughout the length of the line. The actual input
  impedance of a mis-terminated line however, can vary radically
  depending on its length; and so impedance on its own is not sufficient
  to determine the required power ratio. The key to reflectometry
  therefore, is to devise bridges which can measure some quantity
  which is conserved regardless of the length of the line, and
  to derive the required information from that.
       Consider a wave traveling from
  generator to load in a lossless transmission line. As the wave
  moves along the line, it has no knowledge of the conditions it
  will meet when it arrives at the load; and so the relationship
  between voltage and current in the forward traveling wave is
  dictated entirely by the surge resistance (i.e., the characteristic
  resistance), R
0, of the line. Thus we
  may write:
  
  
  
  If the line is not terminated in its characteristic resistance,
  only part of the energy in the wave will be absorbed (or perhaps
  none if the line is open or short-circuit), and a reflected wave
  will be launched on a journey from the load to the generator.
  This reflected wave will also have no knowledge of the conditions
  which prevail at its destination, and so the relationship between
  voltage and current will also be determined solely by R
0, i.e., 
  
In this case, a minus sign is required in order to maintain
consistency in the definitions of the forward and reflected waves;
i.e., we must assume that either the voltage or the current is
reversed relative to the forward wave at the reflection boundary.
To understand this point, note that if the line is open circuit,
a voltage may exist at the discontinuity, but the sum of forward
and reflected currents must be zero, i.e., the sign of the current
must reverse as the wave turns around and heads back towards
the generator. Conversely, if the line is short circuit, then
a finite current may exist at the end of the line, but the sum
of the forward and reflected voltages must be zero, i.e., the
sign of the voltage must reverse. When partial reflection occurs,
the voltage reverses relative to the forward wave if the magnitude
of the load impedance is less than R
0,
and the current reverses if the magnitude of the load impedance
is greater than R
0; but the minus sign
in the expression above maintains consistency in either case,
and allows the forward and reverse wave definitions to be combined
(i.e., to be used as simultaneous equations). 
     We cannot, of course, measure the
forward and reflected voltages and currents independently. If
we make measurements of voltage and current at various points
on the line, we will always measure the sum of forward and reflected
voltages and the sum of forward and reflected currents at each
point. At the load however, we 
can determine the relative
magnitudes of the forward and reflected voltages or currents,
because the relationship between the total voltage and the total
current at this point is defined by the load impedance 
Z.
The ratio so determined is called the 
reflection coefficient,
and is true of the magnitudes of the forward and reflected voltages
and currents at any point in the line because the power (energy
per unit of time) in the forward and reflected traveling waves
is constant. An expression for the reflection coefficient can
be determined as follows:
  If 
V is the voltage across the load, and 
I is the
  current flowing through the load, then we may write:
  
  
    
      | V = I Z = VF
      + VR . . . (3) | 
  
  i.e., the voltage at the load is the sum of the voltages
  in the forward and reflected waves. Similarly, the current flowing
  in the load is the sum of the forward and reflected currents,
  and we may also write:
  
      
      | I = V / Z = IF
      + IR . . . (4) | 
  
  
  The observations made so far are summarised in the diagram
  below:
  
  
    
 
      
    
      From the relationships given above, we have 
IF=
VF/R
0 and 
      
IR=-
VR/R
0. Substituting these expressions into equation
     (
4) gives:
      
     
I = (
VF / R
0) - (
VR / R
0) = (
VF - 
VR) / R
0
     
     and using (
3) gives:
     (
VF + 
VR)
     / 
Z = (
VF - 
VR) / R
0
     which can be rearranged as follows:
     (
VF + 
VR)
     R
0 = (
VF
     - 
VR) 
Z
     VF R
0 + 
VR R
0 = 
VF Z - 
VR
     Z
     VR R
0 + 
VR Z = 
VF
     Z - 
VF R
0
     VR (
Z + R
0)
     = 
VF (
Z - R
0)
     To give:
     
       
         | VR / VF
         = (Z - R0) / (Z + R0) | 
     
     which says that the ratio of the voltages in the reflected
     and forward waves is a system constant which depends only on
     
Z and R
0. Recall however, that
     while this expression is true at the load, it is only true of
     voltage 
magnitudes at other points in the line, and so
     to generalise it we must write: 
       
         | |VR| / |VF|
         = |Z - R0| / |Z + R0| | 
     
which is true everywhere in the line. 
     
 
  The quantity |
VR|/|
VF| is the desired reflection coefficient, and
 is variously given the symbol ρ (rho), Γ (capital Gamma),
 or k, depending on the commentator. Here we will prefer Γ,
 because ρ is already used elsewhere to denote both resistivity
 and density. Γ is sometimes called the "voltage reflection
 coefficient", but this is a peculiar affectation as we may
 see by using relationships (
1)
 and (
2) to eliminate all
 voltages from equation (
3);
 and then using equation (
4)
 to eliminate 
I. By so doing we obtain:
 
IF Z + 
IR
 Z = 
IF R
0
 - 
IR R
0
 which rearranges to:
 
   
     | -IR / IF
     = (Z - R0) / (Z + R0) | 
 
The minus sign is lost in generalising to all points
 on the line (i.e., by taking magnitudes), because |-
IR|= |
IR| , and
 so:
   
     | |IR| / |IF|
     = |Z - R0| / |Z + R0| | 
 
 
  Thus, to summarise:
  
    
      | Γ = | |VR| |VF|
 | = | |IR| |IF|
 | = | | Z - R0 | |
      Z + R0 |
 |  | 
  
  
  
  
    >>> work in progress
    
  
    Lossy lines:
      
Z0 = R
0
      + 
jX
0 (X
0
      is negative) and 
Z0*
  
      Return loss = 20Log
10( 1/Γ )   [dB]
  
      SWR 
      S=Max peak voltage/min peak voltage = Max peak current/min peak
      current
      (Only strictly defined for lines of λ/4 and longer)
  
      S = ( 1+Γ ) / ( 1-Γ )
      True for any length of line and for lossy lines.
  
      Γ = (S-1)/(S+1) 
  
      Γ = √(P
R/P
F)
      
      
      >>>
        
            
Directional coupler:
            The transmission line between a radio transmitter and an antenna
            does not necessarily need to be matched; but the presence of
            standing waves on an unmatched line creates a problem of power
            measurement when the intrumentation (as is usually desirable)
            is located in the radio room. The line performs an impedance
            transformation such that, at a distance of λ/4 (an electrical
            quarter-wavelength, or 90 electrical degrees) from the load,
            the impedance looking into the line will be of high magnitude
            if the magnitude of the load impedance is less than the characteristic
            resistance of the line, and vice versa. The impedance varies
            cyclically as the distance from the load increases, and returns
            to the same value (neglecting losses) at intervals of λ/2.
            Since the length of the line is usually dictated by the physical
            installation rather than by electrical considerations; early
            attempts to monitor transmitter performance by measuring either
            the voltage or the current at the transmitter terminals were
            bound to produce inconsistent results. 
        
        
        
            >>
            Invention of: (early patents). Overcoming misleading measurements
            by taking average of voltage and current analogs at a given point.
        
            Gothe, Buschbeck, Kautter 1939, 
US 2165848 .
            Alexander 1949 US 
2467648 .
        
        
            the directional coupler is related to the telephone hybrid circuit,
            a device used for separating and recombining upstream and downstream
            signals in long telephone lines so that the separated signals
            can be passed through amplifiers. Also used to reduce side tone,
            so that callers are not deafened by their own voices. The name
            'hybrid' probably derives from the fact that any particular transformer
            winding is neither a primary or a secondary, but performs both
            functions simultaneously.
        
        
            Determining Γ as an analog computation problem. 
            
        
          
            
              | Γ = | |VR| |VF|
 | = | |IR| |IF|
 | = | | Z - R0 | |
              Z + R0 |
 | = | | Vv - Vi | | Vv
              + Vi |
 |  | 
          
        
      
      
        >>>>> to be rewritten
          
          
            
6.4-x. The Reflectometer (or SWR) bridge:
              An SWR bridge is a reflectometer bridge with a meter scale calibrated
              in SWR. A reflectometer bridge is a set of two impedance bridges;
              one used normally, and one used with the generator and the load
              transposed. 
                   When an impedance bridge is designed
              to balance at the characteristic resistance (R
0)
              of a transmission line into which it is inserted, the balance
              condition, by definition, occurs when the power reflected back
              from the load is zero; i.e., the bridge indicates whether or
              not the transmission line is correctly terminated, and it transpires
              that any imbalance reading is proportional to the square-root
              of the reflected power. If the load and the generator are transposed
              however, the bridge will no longer balance, because the output
              at the detector port is now 
Vv+
Vi rather than 
Vv-
Vi (the polarity of the current sample is reversed).
              The configuration is still useful however, because it solves
              the problem of how to measure the forward power in a transmission
              line in the presence of standing waves. If there is reflected
              energy travelling in a line, the voltage on the line will be
              the sum of the voltages due to forward and reflected power, and
              this will vary sinusoidally with the distance from the load.
              Hence, if the forward power is to be measured at an arbitrary
              point on the line, it cannot be calculated from |
V|²/R
0. Similarly, the current in the line will
              vary sinusoidally, and the forward power cannot be calculated
              from |
I|²R
0. Current maxima
              however will always correspond to voltage minima, and vice versa,
              and so the forward power can be deduced by making two determinations,
              one from the current and one from the voltage, and taking the
              average. Hence |
Vv+
Vi| is proportional to the square root of the
              forward power, provided that the current and voltage samples
              are taken at exactly the same electrical point on the line. 
                   In a current-transformer bridge
              with more than one turn in the current-transformer primary winding,
              an apparently sensible point at which to sample the voltage is
              at a primary centre tap. Since most bridges only have one primary
              turn however, the voltage must be taken from one side or the
              other, but the error which results is negligible provided that
              the distance from the middle of the current transformer is small
              in comparison to one wavelength at the highest frequency of operation.
              Such is the accepted practice, but in fact it is not always best
              to sample voltage and current at exactly the same physical point;
              because it takes time for the current sample to propagate out
              of the transformer coil. The best technique is to take voltage
              and current samples from points of equal time-delay ralative
              to the source, a matter which can be dealt with by neutralisation,
              or by moving the sampling point down-line by an electrical distance
              equal to half the electrical length of the current-transformer
              secondary winding.
                   A prototype SWR bridge is shown
              below: where the magnitude of 
Vf
              is proportional to the square-root of the forward power and is
              independent of reflected power; and the magnitude of 
Vr is proportional to the square-root of the
              reflected power, and is independent of forward power.
              
                
                  
 
            
              
              Since the output of the current transformer is shared between
              two bridges, the balance condition is now:
              
Vv - 
Vi/2
              = 0
              This means that the voltage sampling network components must
              be chosen to give half the output required for a single bridge,
              but the bridge design procedure is otherwise the same.
          
              
Caveat: Notice that the dual bridge circuit shown
              above has a 
serious flaw in one of its most popular
              implementations; which is that in which the voltage sampling
              network 
Z1, 
Z2
              is a high-impedance capacitive potential divider, the forward
              and reflected output ports are terminated with diode detectors,
              and the circuit is used to drive two meters simultaneously. When
              the load 
ZL is correctly matched
              to the cable, the forward output will be large and will drive
              its detector hard; causing the output of the voltage sampling
              network to droop, especially at low frequencies. This will throw
              the balance condition for the reflected power bridge and give
              rise to a spurious reading. Essentially, 
the shared capacitive-divider
              version does not work properly at low frequencies when
              used to drive two separate meters, it being an ill-conceived
              extension of a circuit intended to have a single meter and a
              switch to select between forward and reverse readings. Warren
              Bruene's solution to this problem was to use separate voltage
              sampling networks for the two bridges [
40]. Also, if we
              decide to compensate for current-transformer delay by moving
              the voltage sampling point along the line, we will need to move
              the reflected power voltage network towards the load and the
              forward power voltage network towards the generator, and so we
              will be forced to use two voltage sampling networks anyway. Another
              solutions are to use a voltage sampling network with a low output
              impedance.
                   It was mentioned in the last paragraph,
              that in order to delay the voltage sample for reflected power,
              it is necessary to move the sampling point 
towards the load.
              This might seem anti-intuitive, but only if we subscribe to the
              view that the reflectometer can measure reflected power. It can
              do no such thing: it can only infer the existence of reflected
              power from the difference between the actual load impedance and
              the target load impedance. To understand this point, consider
              an SWR bridge designed to balance when the load is 50+
j0Ω.
              If we connect this bridge directly to a 100Ω load resistor,
              it will declare an SWR of 2:1. The resistor is not reactive however,
              and so will absorb all of the power delivered to it and reflect
              none. The 2:1 SWR reading is only true when the bridge sees an
              impedance magnitude of 100Ω (or 25Ω) at the input
              to a 50Ω transmission line. The bridge is just an impedance
              bridge, it has no special psychic powers, and its readings are
              only true when it is inserted into a line having the same characteristic
              resistance.
              
              
              
              
6.4-x. The Bruene Directional Wattmeter:
                
                    >>> To be rewritten.
                    >>>> The Bruene bridge is discussed below because
                    it is historically interesting. It is not recommended as a basis
                    for modern designs.
                
                
                    The "Directional Wattmeter" (i.e., SWR bridge) circuit
                    shown below is based on a circuit devised by Warren Bruene (W0TTK,
                    W5OLY, of the Collins Radio Company) which became popular among
                    radio amateurs as a result of an article published in 1959 [
40].
                    The original Bruene bridge was essentially the same as Douma's
                    bridge, but without low-frequency compensation and rearranged
                    to use the shunt-diode detector configuration [see Detectors
                    for RF meas.]. These changes were sufficient to circumvent Douma's
                    1957 patent [USP 2808566], but the circuit is also a logical
                    development of the capacitor ratio-arm bridge (CRAB) used in
                    earlier Collins designs and so may well have been invented independently.
                    The CRAB used as a mismatch (SWR) indicator in the Collins 180L-3
                    (2 MHz - 25 MHz) automatic antenna tuner is discussed elsewhere
                    [ /zdocs/zmatching/ ]. A "high-frequency iron" toroidal
                    current transformer was however used for the phase and magnitude
                    bridges of that unit, and so it was only a matter of time before
                    the toroid migrated into the reflectometer. The CRAB was used
                    down to 2 MHz however (limited only by the output impedance of
                    the ratio arms); whereas the lack of LF compensation in the original
                    Bruene bridge raised the useful minimum frequency, and the designs
                    discussed in references [
40], [
41], and [
42]
                    are only suitable for 3.5-30 MHz. Douma's patent expired in 1977,
                    and so, while home constructors never had valid reason to omit
                    the compensation resistors (apart from lack of awareness of their
                    importance), commercial designers now have no reason to omit
                    them either (and probably never did, because Douma did not invent
                    this compensation method - it was used by Korman in 1942 [US
                    Pat. 2285211] and so was out-of-Patent by 1962). Consequently,
                    the resistors (R
v) have been added to
                    the circuit shown below, and their inclusion should be regarded
                    as mandatory. The inclusion of compensation resistors also necessitates
                    the inclusion of blocking capacitors (C
b)
                    to prevent the DC outputs of the detectors from being shunted
                    to ground. C
b merely needs to have a low
                    reactance at the minimum frequency of operation (10 nF ceramic
                    will usually do the trick) but an excessively large capacitor
                    (i.e., several μF) in this position will slow the rate at
                    which the DC output can change and will damp the meter response.
                    
                      
                      
 
                        
                          
                          Notice that the shunt-diode detector is connected directly between
                          the current and voltage sample outputs and the rectified signal
                          is extracted through an RF choke (RFC). This floating detector
                          configuration is a Hallmark of the Collins Radio Company from
                          the 1950s; but is perhaps nowadays somewhat archaic. One disadvantage
                          is that the detector 'ports' are not referenced to ground, and
                          so isolation transformers will be required if signals are to
                          be injected into them. Note also that the RF chokes must be carefully
                          chosen to have a very high impedance throughout the operation
                          frequency range, since reactive loading of the voltage sampling
                          network will introduce 
serious errors into the balance
                          condition (multi-segment RF chokes of 1mH or more are normally
                          used). If the drop in meter sensitivity which results from using
                          R
v as the detector DC return path can
                          be tolerated, it is a good idea to swap the detector connections,
                          i.e., connect the anode of the diode to the junction of C
1 and C
2, and connect
                          the blocking capacitor C
b to the current
                          transformer output. Due to the very low output impedance of the
                          current transformer circuit, self-capacitance effects in the
                          choke will then only affect the magnitude of the meter reading
                          and will have little effect on the balance condition. If the
                          detector is reversed in this way incidentally, attempting to
                          restore its sensitivity by connecting a choke across R
v
                          is not a good idea; but as we shall see by performing an actual
                          design calculation, the loss of sensitivity will not be particularly
                          large because R
v will be measured in hundreds
                          rather than thousands of ohms.
                      
                          The balance condition is:
                      
                          
Vv - 
Vi/2
                          = 0
                      
                          where, from the derivation given in 
section
                          ?:
                      
                          
Vv/
V = 
ηv = (R
v // 
jX
C1 // 
jX
C2) /
                          
jX
C2
                      
                          and the current transfer function at balance (from 
section
                          ?) is:
                      
                          
Vi/
V = 
η0 = (
jX
Li //
                          R
i) / N
i R
0
                      
                          Since the current sample is shared by two bridges, we must divide
                          it by two. Hence, at balance:
                      
                          
ηv = 
η0/2
                      
                          i.e.,
                      
                          (R
v // 
jX
C1
                          // 
jX
C2) / 
jX
C2
                          = (
jX
Li // R
i)
                          / (2 N
i R
0)
                      
                          which upon inversion of both sides gives:
                      
                          
jX
C2 [(1/
jX
C1)
                          + (1/
jX
C2) + (1/R
v)]
                          = 2N
i R
0 [(1/R
i) + (1/
jX
Li)]
                      
                          Recalling that X
C=-1/2πfC and 1/
j=-
j,
                          this rearranges to:
                      
                          [(C
1+C
2)/C
2] + 
jX
C2/R
v = [2N
i R
0
                          / R
i] - 
j2N
i R
0/X
Li
                      
                          Hence, equating the real parts:
                      
                          
                            
                              | (C1+C2)/C2 = 2Ni R0/Ri | x.1 | 
                            
                            
                                  and, equating the imaginary parts:
                              
                                  
                                  
                                    
                                    Example:
                                    
                                    A Bruene bridge design is given in ref. [
41]. This uses
                                    an Amidon T68-2 core with 35 turns of #26AWG enamelled wire,
                                    and the current transformer secondary load is 20 Ω, i.e.,
                                    the two resistors marked R
i/2 above are
                                    10 Ω each. The capacitors here designated C
1
                                    were originally 330 pF, and capacitors C
2
                                    were 7 pF trimmers. Low-frequency compensation resistors were
                                    not used in the original circuit, and the operating frequency
                                    range was stated to be 3.5 to 30 MHz; but since we have data
                                    for the transformer core we can compute values for the compensation
                                    resistors and extend the frequency range to 1.8 MHz. 
                                
                                    Using equation (
x.1) we will
                                    first find the nominal capacitance of C
2
                                    when the bridge is balanced for 50 Ω loads:
                                    (C
1/C
2) + 1 = 2N
i R
0 / R
i
                                    = 2×35×50/20 = 175
                                    C
1/C
2 = 174
                                    330 pF = 174C
2
                                    C
2 = 1.90 pF
                                    This has a reactance of -24 kΩ at 3.5 MHz and -46.6 kΩ
                                    at 1.8MHz. To stay roughly in keeping with the original design
                                    intentions we should increase C
2 to obtain
                                    a reactance of about -24 kΩ at 1.8 MHz, and so a candidate
                                    value for C
2 is 3.68 pF and C
1=174C
2=641 pF. 680 pF is the larger nearest preferred
                                    value, and 1% silvered-mica capacitors of this value are available,
                                    and so we end up with C
1=680 pF, C
2=680/174=3.9 pF (obtained by adjusting a 2-10pF
                                    trimmer). Since there are two voltage sampling networks, our
                                    choice will result in a fixed capacitance of nearly 8 pF across
                                    the generator, but since one of the networks is on the load side,
                                    it will be absorbed into the load impedance after adjustment.
                                    Hence the mismatch seen by the generator when the bridge is balanced
                                    will be mainly due to the presence of only one of the voltage
                                    sampling networks, and the effect of 3.9 pF is comfortably within
                                    normal load tolerance limits.
                                
                                    For low frequency compensation, we note that the transformer
                                    has 35 turns, and the A
L value of the
                                    T68-2 core is 5.7 nH. Hence the secondary inductance is A
LN²=7 μH. Using equation (
x.2): 
                                    R
v = L
i/2N
i R
0C
2
                                    = 7×10
-6 / ( 2 × 35 × 50 ×
                                    3.9×10
-12 ) = 512 Ω 
                                    A measurement of the actual inductance of the transformer coil
                                    is, of course, a better criterion for the calculation of the
                                    compensation resistor.
                                
                                    In the matter of setting the balance points and calibrating such
                                    a bridge, notice that the circuit is completely symmetric. Having
                                    connected a 50 Ω resistor to the load port and adjusted
                                    the reflected-signal voltage-sampling network for a null reading
                                    on the corresponding meter, the generator and load connections
                                    can be swapped for adjustment of the other trimmer. For calibration
                                    of the meter scales, the voltage across the load can be measured
                                    (e.g., using a calibrated oscilloscope and a ×10 probe,
                                    provided that the 'scope input voltage rating is not exceeded),
                                    swapping the generator and load connections as before for adjustment
                                    of the two meter series resistors. For very high-power transmitters,
                                    the voltage should be measured at the output of a through-line
                                    attenuator (i.e., a tapped dummy-load resistor). Recall that
                                    forward power is proportional to the square root of 
Vv+
Vi, and so
                                    the meters will have to be fitted with non-linear scales if calibrated
                                    in watts or relative power. It is quite common for the meter
                                    resistors to be switched for different FSD power readings. Dual-gang
                                    variable potentiometers are also used, but the tracking of inexpensive
                                    double potentiometers, particularly of the logarithmic variety,
                                    is notoriously bad. Since most transmitters have a drive-level
                                    control, infinite variability of the bridge sensitivity is not
                                    usually needed, and switched ranges calibrated in actual power
                                    are much more useful. Note that the accuracy of the calibration
                                    at low frequencies depends on the relationship between X
Li and R
i as discussed
                                    in 
section ?. In the example
                                    given above X
Li=4R
i
                                    at 1.8 MHz, and so the error will be less than 5% (see 
table ?); but in that case the
                                    design is for use in conjunction with kilowatt transmitters,
                                    and more sensitive designs (less turns on the current transformer
                                    core or a larger value of secondary load resistance) will not
                                    be so good in this respect.
                                
                                
                                
                                    >>>>>
                                    Use of transformers to take off |
Vv±
Vi |. Gets rid of the chokes and costs about the same.
                                    
                                
                                    >>>>
    
  Refs
  
  [
40] 
"An Inside Picture
  of Directional Wattmeters", Warren B Bruene W0TTK [W5OLY],
  QST April 1959 p24-28.
  [
41] 
"In-Line RF Power
  Metering" Doug DeMaw W1CER [W1FB], QST Dec 1969 p11-
  16.
  Construction article for Bruene-type bridges for 3.5-30MHz.
  [
42] 
Ferromagnetic Core
  Design & Application Handbook, M F "Doug" DeMaw
  W1FB, 1st edition, 2nd printing 1996. MFJ publishing co. http://www.mfjenterprises.com/ .
  
  Bruene bridge: p94-95.
  
    
  
    
      6.4-x. SWR Bridge with load-side voltage sampling.
      
      
         
        
          
            >>>>>
            Same basic design considerations as Bruene.
            Inductance of half winding is L
i /2 as
            explained in section 6-x.
            Gets rid of the chokes.
            Gets rid of the loading defect of shared voltage-sampling networks.
            CVS network across load allows neutralisation by the load-capacitance
            method. HF phase neutralisation can be effected by arranging
            CVS network capacitance to be larger than required, then adding
            a small amount of capacitance across the transformer secondary.
        
            HF amplitude correction (compensation for inductance of lower
            voltage-sampling arm) can be effected by placing a small inductance
            in series with C2.
            Ground referenced det. ports allow reciprocal calibration and
            stealth tuning (must short L
α during the calibration
            reversal)
            L
α calculated as per section 6-x, compensates
            for capacitance across the line.
            Rv can be a resistor in series with small pot.
            C1 can be a fixed capacitor in parallel with a trimmer.
            
              
 
                
               Power Measurement
                
                
                6.4-x. Square-Law detectors:
              
              
              
                Power Measurement
                
                
                6.4-x. Square-Law detectors:
                  
                      A section on the use of square-law detectors in power measurement.
                  
                      Large signal "linear" detector. 
                      
                      Small signal. Output voltage is proportional to the square of the input voltage
                      
                      Agilent application notes [see 
diode detectors].
                      
                      The square root of a number can be obtained by halving its logarithm and taking the antilog. 
                      
                      Log and antilog amplifiers. Temp compensation using dual transistors.
                      
                  
                      >>
                      
© D W Knight 2008, 2013.
  
David Knight asserts the right to be recognised as the author of this work.
  
  
  Last edited:2021 Sept 12
th (but still not conforming to HTML 5)